Calculadora de Resistencia de Puesta a Tierra Gratis

Calcula la resistencia de sistemas de puesta a tierra. Ingresa resistividad del suelo y configuración de electrodos.

ohm-m
m
mm

Ground Resistance

35.12 ohm

Ground Resistance vs Soil Resistivity (rho)

Fórmula

## Ground Rod Resistance The resistance of a ground rod depends on soil resistivity and rod geometry. ### Formula (simplified for vertical rod) **R = (rho / 2 pi L) ln(4L / d)** where rho is soil resistivity in ohm-metres, L is rod length, d is rod diameter, and ln is the natural logarithm. Lower resistance is better for safety. Most codes require < 5 ohms for power systems and < 25 ohms for lightning protection.

Ejemplo Resuelto

A 3 m x 16 mm ground rod in soil with 100 ohm-m resistivity.

  1. 01d = 0.016 m
  2. 02ln(4 x 3 / 0.016) = ln(750) = 6.62
  3. 03R = 100 / (2 x pi x 3) x 6.62 = 100/18.85 x 6.62 = 35.12 ohm
  4. 04This exceeds 5 ohm. Multiple rods or soil treatment may be needed.

Preguntas Frecuentes

What is typical soil resistivity?

Wet clay: 10-100 ohm-m. Sandy loam: 50-300 ohm-m. Dry sand: 500-5000 ohm-m. Gravel: 1000-5000 ohm-m. Rock: 2000-100,000 ohm-m. Moisture and mineral content have the strongest effect.

How do I reduce ground resistance?

Use longer rods (doubling length reduces R by about 40%), multiple rods spaced apart (parallel combination), chemical soil treatment (bentonite, conductive cement), or ground enhancement materials.

How is soil resistivity measured?

The Wenner four-pin method (ASTM G57) is standard. Four equally spaced pins are driven into the soil and resistance is measured between the inner pair while current flows through the outer pair.