Calculadora de Corriente de Cortocircuito Gratis

Calcula la corriente de cortocircuito en un punto del sistema eléctrico. Esencial para protección y coordinación.

kVA
V
%

Prospective Short-Circuit Current

14,434 A

Full Load Current721.7 A
Short-Circuit Current14.43 kA

Prospective Short-Circuit Current vs Transformer Rating

Fórmula

## Transformer Short-Circuit Current The prospective short-circuit current at the transformer secondary is limited by the transformer impedance. ### Formulas **I_FL = kVA x 1000 / (sqrt(3) x V)** (full load current) **I_SC = I_FL / (Z%/100)** (short-circuit current) where Z% is the transformer impedance expressed as a percentage. This is the maximum fault current available at the transformer terminals, ignoring cable impedance downstream.

Ejemplo Resuelto

A 500 kVA transformer, 400 V secondary, 5% impedance.

  1. 01I_FL = 500,000 / (1.732 x 400) = 721.7 A
  2. 02I_SC = 721.7 / 0.05 = 14,434 A = 14.43 kA
  3. 03Switchgear must have a breaking capacity above 14.43 kA.

Preguntas Frecuentes

Why does transformer impedance matter?

Higher impedance limits short-circuit current (reducing switchgear cost) but increases voltage regulation (more voltage drop under load). Typical impedance: 4-6% for distribution transformers.

Does cable impedance reduce fault current?

Yes. Cable resistance and reactance add to the total impedance, reducing the fault current at points downstream of the transformer. Use I_fault = V / Z_total for accurate calculations.

What is the asymmetric peak current?

The first half-cycle of fault current includes a DC offset that can increase the peak to 1.8-2.5 times the RMS value. Equipment must withstand this momentary peak, expressed as the peak making capacity.

Aprender

Beam Stress Calculation Guide: From Theory to Practice

Calculadoras Relacionadas