## Three-Phase Power Calculations

Three-phase systems are the standard for industrial and commercial power distribution.

### Formulas (Balanced Load)

**Apparent Power = sqrt(3) x V_line x I_line**

**Real Power = Apparent x Power Factor**

**Reactive Power = sqrt(Apparent^2 - Real^2)**

**Phase Voltage = Line Voltage / sqrt(3)**

The sqrt(3) factor (approximately 1.732) arises from the 120-degree phase separation between the three phases.

Ejemplo Resuelto

480 V three-phase, 20 A line current, 0.85 power factor.

  1. Apparent: sqrt(3) x 480 x 20 = 16,627 VA = 16.63 kVA
  2. Real: 16,627 x 0.85 = 14,133 W = 14.13 kW
  3. Reactive: sqrt(16627^2 - 14133^2) = 8,744 VAR = 8.74 kVAR
  4. Phase voltage: 480 / 1.732 = 277.1 V