Calculadora de Corrección de Factor de Potencia Gratis

Calcula los capacitores necesarios para corregir el factor de potencia industrial a valores aceptables.

kW

Required Capacitor Bank

55.3 kVAR

Current Reactive Power88.2 kVAR
New Reactive Power32.9 kVAR
Apparent Power Reduction28.1 kVA

Required Capacitor Bank vs Real Power

Fórmula

## Power Factor Correction Low power factor means the utility must deliver more current (and apparent power) than the load actually uses. Capacitor banks supply reactive power locally. ### Formula **kVAR needed = kW x (tan(arccos(PF_current)) - tan(arccos(PF_target)))** ### Benefits - Reduced utility power factor penalties - Lower line current (smaller cables, less loss) - Freed transformer and distribution capacity Most utilities penalize power factors below 0.90. Correcting to 0.95 is a common economic target.

Ejemplo Resuelto

100 kW load at PF 0.75, correcting to PF 0.95.

  1. 01Current angle: arccos(0.75) = 41.41 degrees, tan = 0.8819
  2. 02Target angle: arccos(0.95) = 18.19 degrees, tan = 0.3287
  3. 03kVAR needed: 100 x (0.8819 - 0.3287) = 55.3 kVAR
  4. 04kVA reduction: 100/0.75 - 100/0.95 = 133.3 - 105.3 = 28.1 kVA

Preguntas Frecuentes

What causes low power factor?

Inductive loads like motors, transformers, and fluorescent lighting draw reactive current that lags voltage, reducing power factor.

Can I overcorrect power factor?

Yes. A leading power factor (above 1.0 correction) can cause voltage rise and resonance. Do not exceed PF 0.98-0.99.

Where should capacitors be installed?

At the load for maximum benefit, at the main bus for simplicity, or a combination. Automatic switching banks handle varying loads.

Aprender

Ohm's Law Guide

Calculadoras Relacionadas