Kostenloser Luftfilter-Rechner

Dimensionieren Sie HLK-Filter nach Luftvolumenstrom und Anströmgeschwindigkeit.

CFM
ft/min
in
in

Filters Needed

2

Min Filter Face Area4.00 sq ft
Actual Face Velocity173 ft/min

Filters Needed vs System Airflow

Formel

## Filter Sizing **Face Area = CFM / Face Velocity** **Filters = Face Area / Single Filter Area** Keeping face velocity under 300 ft/min ensures good filtration and low pressure drop. Higher velocities reduce filter life and may blow dust through the media.

Lösungsbeispiel

1,200 CFM system, 300 ft/min max, using 20x25 inch filters.

  1. 01Min face area = 1200 / 300 = 4.0 sq ft
  2. 02Filter area = 20 x 25 / 144 = 3.47 sq ft
  3. 03Filters = ceil(4.0 / 3.47) = 2
  4. 04Actual velocity = 1200 / (2 x 3.47) = 173 ft/min

Häufig Gestellte Fragen

What is ideal filter face velocity?

For standard 1-inch filters: 250-350 ft/min. For 4-inch media filters: 200-300 ft/min. Lower velocities improve filtration and extend filter life.

How often should HVAC filters be replaced?

1-inch filters: every 1-3 months. 4-inch media filters: every 6-12 months. More frequently if you have pets or live in a dusty area.