Calcolatore Corrente di Avviamento Motore

Calcola facilmente i risultati con il Calcolatore Corrente di Avviamento Motore online gratuito.

V
V
VA
%

Turns Ratio (Np:Ns)

4.00

Primary Current10.42 A
Secondary Current41.67 A
Power Loss250.0 W
Output Power4,750 W

Turns Ratio (Np:Ns) vs Primary Voltage

Formula

Transformer Turns Ratio

The turns ratio determines the voltage transformation between primary and secondary windings.

Formulas

Turns Ratio = Vp / Vs = Np / Ns

Ip = VA / Vp and Is = VA / Vs

Current transforms inversely: higher voltage means lower current, preserving power (minus losses).

Power Loss = VA x (1 - Efficiency)

Typical transformer efficiencies range from 90% (small) to 99% (large utility).

Esempio Risolto

480 V to 120 V step-down, 5 kVA, 95% efficient.

  1. 01Turns ratio: 480 / 120 = 4.00:1
  2. 02Primary current: 5000 / 480 = 10.42 A
  3. 03Secondary current: 5000 / 120 = 41.67 A
  4. 04Power loss: 5000 x 0.05 = 250 W
  5. 05Output power: 5000 x 0.95 = 4,750 W

Domande Frequenti

Can a transformer change frequency?

No. A standard transformer passes the same frequency through. To change frequency, use a frequency converter.

What determines transformer efficiency?

Core losses (hysteresis and eddy currents) and copper losses (I^2R in windings). Larger transformers are generally more efficient.

What is VA rating vs watt rating?

VA is apparent power. For purely resistive loads, VA equals watts. For reactive loads, watts = VA x power factor.

Impara

Ohm's Law Guide

Calcolatrici Correlate