मुफ्त सर्किट ब्रेकर साइज़िंग कैलकुलेटर

सही सर्किट ब्रेकर आकार चुनें। विद्युत भार और तार क्षमता के आधार पर उचित ब्रेकर रेटिंग निकालें।

W

Recommended Breaker

25 A

Actual Current Draw20.0 A
Design Current25.0 A

Recommended Breaker vs Total Connected Load

सूत्र

Circuit Breaker Sizing

Amps = Watts / Volts

Continuous load: multiply by 1.25 per NEC 210.20(A). Then round up to the next standard breaker size (15A, 20A, 30A, 40A, 50A, etc.).

हल किया गया उदाहरण

2,400W continuous load on 120V.

  1. 01Amps = 2400 / 120 = 20A
  2. 02Design amps = 20 x 1.25 = 25A
  3. 03Next standard size = 25A, or use 30A breaker

अक्सर पूछे जाने वाले प्रश्न

What makes a load continuous?

A continuous load operates for 3 hours or more without interruption. Examples include lighting, electric heaters, and HVAC equipment.

Can I use the full breaker rating for non-continuous loads?

Yes, non-continuous loads can use up to 100% of the breaker rating. However, mixed circuits with both continuous and non-continuous loads must account for each portion separately.