मुफ्त विद्युत भार कैलकुलेटर

अपने घर या भवन का कुल विद्युत भार निकालें। उपकरणों की वाट क्षमता से कुल लोड की गणना करें।

W
%

Current Draw

12.5 A

With Safety Factor15.6 A
Recommended Breaker20 A

Current Draw vs Total Watts

सूत्र

Electrical Load Formula

Amps = Watts / Volts

NEC Safety Factor = 125% (for continuous loads)

Breaker sizes are standard: 15A, 20A, 30A, 40A, 50A. Always round up to the next standard size.

हल किया गया उदाहरण

1,500W load on a 120V circuit with 125% safety factor.

  1. 01Amps = 1,500W / 120V = 12.5A
  2. 02With safety = 12.5 × 1.25 = 15.6A
  3. 03Recommended breaker = 20A

अक्सर पूछे जाने वाले प्रश्न

What is the NEC 80% rule?

The National Electrical Code requires that continuous loads not exceed 80% of the breaker rating (or equivalently, the breaker should be 125% of the load). A 20A breaker handles 16A continuous.