Calculadora de Retorno de Aire Gratis

Dimensiona las rejillas y ductos de retorno de aire para un sistema HVAC balanceado y eficiente.

CFM
ft/min
%

Gross Grille Area Needed

3.33 sq ft

Grille Area480 sq in
Return Duct Diameter21.4 in

Gross Grille Area Needed vs System Airflow

Fórmula

## Return Air Sizing **Grille Area = CFM / (Velocity x Free Area %)** Return grilles must be large enough to avoid creating excessive negative pressure. The free area percentage accounts for the grille bars or louvers that block part of the opening. Keep return grille velocity below 400 ft/min for quiet operation.

Ejemplo Resuelto

1,000 CFM system, 400 ft/min max grille velocity, 75% free area.

  1. 01Effective velocity = 400 x 0.75 = 300 ft/min
  2. 02Grille area = 1000 / 300 = 3.33 sq ft = 480 sq in
  3. 03Could use two 16x16 in grilles (512 sq in total)
  4. 04Return duct = 2 x sqrt(1000/400/pi) x 12 = 21.4 in

Preguntas Frecuentes

Can I use fewer return grilles than supply registers?

Yes, but each return must handle the total CFM of the zone it serves. Undersized returns cause high static pressure, reduced airflow, and noisy operation.

Should every room have a return?

Ideally yes. At minimum, every room with a door should have a return or a transfer grille to allow air back to the central return. Without this, closed doors create pressure imbalances.