Calculadora de Carga de Refrigerante Gratis
Calcula la carga de refrigerante necesaria para un sistema de aire acondicionado según la longitud de tuberías.
Additional Charge
15.0 oz
Additional Charge vs Total Line Set Length
Fórmula
## Refrigerant Charge Adjustment **Additional Charge = (Line Length - Factory Length) x oz/ft** AC condensing units ship with a factory refrigerant charge that covers a standard line set (typically 25 ft). For every additional foot of liquid line, extra refrigerant must be added per the manufacturer specifications (often 0.6 oz/ft for R-410A).
Ejemplo Resuelto
50 ft line set, factory covers 25 ft, R-410A at 0.6 oz/ft, 96 oz factory charge.
- 01Extra length = 50 - 25 = 25 ft
- 02Additional = 25 x 0.6 = 15.0 oz
- 03Total = 96 + 15 = 111 oz = 6.94 lbs
Preguntas Frecuentes
How do I know the oz per foot for my unit?
Check the manufacturer installation manual. Common values for R-410A are 0.5-0.8 oz/ft depending on the liquid line diameter and system capacity.
Can I have too much refrigerant?
Yes, overcharging causes high head pressure, reduced efficiency, possible compressor damage, and liquid slugging. Always verify charge with superheat or subcooling readings.