Calculadora de Llenado de Conduit Gratis
Calcula el porcentaje de llenado de una tubería conduit según la cantidad y calibre de los cables.
Conduit Fill
45.0 %
Conduit Fill vs Conduit Internal Area
Fórmula
## NEC Conduit Fill Rules The National Electrical Code limits fill percentages to prevent overheating: - **1 conductor: 53%** - **2 conductors: 31%** - **3 or more: 40%** Calculate fill by dividing total conductor area (including insulation) by the conduit internal area.
Ejemplo Resuelto
4 conductors of 12 AWG THHN (0.0973 sq in each) in 3/4-inch EMT (0.864 sq in).
- 01Total wire area = 4 x 0.0973 = 0.389 sq in
- 02Fill = 0.389 / 0.864 x 100 = 45.0%
- 03NEC allows 40% for 3+ conductors
- 04This conduit is overfilled; upsize to 1-inch EMT.
Preguntas Frecuentes
Where do I find wire and conduit areas?
NEC Chapter 9, Tables 4 and 5 list internal areas for common conduit types and conductor areas with insulation by wire type and gauge.
Do ground wires count toward fill?
Yes, equipment grounding conductors must be included in the fill calculation. Only internal conduit nipples 24 inches or less are exempt from the 40% rule.