Air Changes Rechner — Formel
Air Changes per Hour (ACH)
ACH defines how many times the entire room volume of air is replaced per hour.
Formula
Airflow = Room Volume x ACH
Required ACH depends on the room function. Adequate ventilation controls temperature, humidity, odours, and airborne contaminants.
Lösungsbeispiel
A 10m x 6m x 3m room requiring 6 air changes per hour.
- Volume = 10 x 6 x 3 = 180 m^3
- Airflow = 180 x 6 = 1080 m^3/h
- Airflow = 1080 / 3.6 = 300 L/s