Surge Protection Rechner
Berechnen Sie SPD energy absorption und clamping voltage requirements for lightning und surge protection.
8/20 microsecond is standard test waveform
Clamping V / System V peak; typical MOV = 2-3x
Clamping Voltage
813 V
Clamping Voltage vs Surge Duration
Formel
Surge Protection Device Sizing
SPDs must absorb surge energy while limiting voltage to a safe clamping level that protects downstream equipment.
Formulas
V_clamp = V_peak x Clamping Ratio
Energy = V_clamp x I_surge x Duration
The standard test waveform for SPDs is 8/20 microseconds (8 us rise, 20 us to half-value).
SPD Categories (IEC 61643)
Lösungsbeispiel
230 V system, 10 kA surge (8/20 us), MOV clamping ratio 2.5x.
- 01System peak: 230 x sqrt(2) = 325 V
- 02Clamping voltage: 325 x 2.5 = 813 V
- 03Energy: 813 x 10,000 x 20e-6 = 162.6 J
- 04Peak power: 813 x 10 = 8,130 kW
Häufig Gestellte Fragen
What is an 8/20 microsecond waveform?
A standard test surge that rises to peak in 8 microseconds and decays to half-value in 20 microseconds. It simulates induced lightning surges.
How do I choose between MOV and TVS?
MOVs handle high energy and are used in power systems. TVS diodes have faster response and lower clamping, ideal for sensitive electronics.
How many surges can an SPD handle?
MOV-based SPDs degrade with each surge. Rating should include expected surge count over the device lifetime, with replacement indicators.