Kostenloser Lüftungsrate-Rechner
Berechnen Sie die Außenluftzufuhr nach ASHRAE 62.1.
sq ft
people
CFM
CFM
Total Outdoor Air
110 CFM
People Component50 CFM
Area Component60 CFM
Total Outdoor Air vs Floor Area
Formel
## ASHRAE 62.1 Ventilation **Outdoor Air = (People x CFM/person) + (Area x CFM/sqft)** ASHRAE 62.1 uses a two-part calculation: a per-person rate for bioeffluents and a per-area rate for building emissions. Office spaces typically use 5 CFM/person and 0.06 CFM/sqft.
Lösungsbeispiel
1,000 sq ft office with 10 occupants.
- 01People = 10 x 5 = 50 CFM
- 02Area = 1000 x 0.06 = 60 CFM
- 03Total = 50 + 60 = 110 CFM outdoor air
Häufig Gestellte Fragen
Why are there two components?
The per-person rate handles CO2 and odors from occupants. The per-area rate addresses off-gassing from building materials, furniture, and finishes regardless of occupancy.
Is this the total supply air?
No, this is only the outdoor (fresh) air portion. Total supply air also includes recirculated air needed for temperature control, which is typically much higher.