Kostenloser Anschlusswert-Rechner
Berechnen Sie die gesamten Anschlusswerte für die Sanitärplanung.
Total Fixture Units
15.5 WSFU
Estimated Peak Demand19.7 GPM
Total Fixture Units vs Toilets (Flush Valve)
Formel
## Fixture Unit Method Each plumbing fixture is assigned a unit value based on its flow demand. The total WSFU determines minimum pipe size per code tables. A quick estimate for peak demand in GPM uses the Hunter curve approximation: **GPM = 5 x sqrt(WSFU)**.
Lösungsbeispiel
2 toilets, 3 sinks, 2 showers, 1 dishwasher, 1 washer.
- 01Toilets: 2 x 2.5 = 5
- 02Sinks: 3 x 1 = 3
- 03Showers: 2 x 2 = 4
- 04Dishwasher: 1 x 1.5 = 1.5
- 05Washer: 1 x 2 = 2
- 06Total = 15.5 WSFU
- 07Peak GPM = 5 x sqrt(15.5) = 19.7 GPM