Calcolatore Ricambi d'Aria Gratuito

Calcola la portata d'aria esterna secondo la normativa ASHRAE 62.1.

sq ft
people
CFM
CFM

Total Outdoor Air

110 CFM

People Component50 CFM
Area Component60 CFM

Total Outdoor Air vs Floor Area

Formula

## ASHRAE 62.1 Ventilation **Outdoor Air = (People x CFM/person) + (Area x CFM/sqft)** ASHRAE 62.1 uses a two-part calculation: a per-person rate for bioeffluents and a per-area rate for building emissions. Office spaces typically use 5 CFM/person and 0.06 CFM/sqft.

Esempio Risolto

1,000 sq ft office with 10 occupants.

  1. 01People = 10 x 5 = 50 CFM
  2. 02Area = 1000 x 0.06 = 60 CFM
  3. 03Total = 50 + 60 = 110 CFM outdoor air

Domande Frequenti

Why are there two components?

The per-person rate handles CO2 and odors from occupants. The per-area rate addresses off-gassing from building materials, furniture, and finishes regardless of occupancy.

Is this the total supply air?

No, this is only the outdoor (fresh) air portion. Total supply air also includes recirculated air needed for temperature control, which is typically much higher.