Calcolatore Dimensionamento Interruttore Gratuito

Calcola la taglia dell'interruttore automatico in base al carico del circuito.

W

Recommended Breaker

25 A

Actual Current Draw20.0 A
Design Current25.0 A

Recommended Breaker vs Total Connected Load

Formula

## Circuit Breaker Sizing **Amps = Watts / Volts** **Continuous load: multiply by 1.25** per NEC 210.20(A). Then round up to the next standard breaker size (15A, 20A, 30A, 40A, 50A, etc.).

Esempio Risolto

2,400W continuous load on 120V.

  1. 01Amps = 2400 / 120 = 20A
  2. 02Design amps = 20 x 1.25 = 25A
  3. 03Next standard size = 25A, or use 30A breaker

Domande Frequenti

What makes a load continuous?

A continuous load operates for 3 hours or more without interruption. Examples include lighting, electric heaters, and HVAC equipment.

Can I use the full breaker rating for non-continuous loads?

Yes, non-continuous loads can use up to 100% of the breaker rating. However, mixed circuits with both continuous and non-continuous loads must account for each portion separately.