UPS बैटरी साइज़िंग कैलकुलेटर — सूत्र
UPS Battery Sizing
Proper battery sizing ensures the UPS provides the required runtime at the expected load.
Formula
Capacity (Ah) = (Load / Efficiency) x Runtime (hours) / Battery Voltage / DOD
Where DOD is the maximum depth of discharge (80% for lead-acid to extend life, 90% for lithium).
Sizing Considerations
हल किया गया उदाहरण
2000 W load, 30 min runtime, 48 V battery, 90% inverter efficiency, 80% DOD.
- Runtime in hours: 30 / 60 = 0.5 hours
- Actual draw: 2000 / 0.90 = 2222 W
- Capacity: 2222 x 0.5 / 48 / 0.80 = 28.9 Ah
- Energy: 2222 x 0.5 / 0.80 / 1000 = 1.39 kWh
- Discharge current: 2222 / 48 = 46.3 A