## Estimating Short Circuit Current

The maximum short-circuit current at a transformer secondary determines the required interrupting capacity of protective devices.

### Formula

**I_sc = I_fla / (Z% / 100)**

Where I_fla is the transformer full-load secondary current and Z% is the transformer impedance.

**I_fla (3-phase) = kVA x 1000 / (sqrt(3) x V_secondary)**

This gives the maximum available fault current at the transformer terminals. Downstream cable impedance reduces the fault current at the load.

हल किया गया उदाहरण

500 kVA transformer, 5% impedance, 480 V secondary.

  1. FLA: 500,000 / (1.732 x 480) = 601.4 A
  2. I_sc: 601.4 / 0.05 = 12,029 A = 12.0 kA
  3. Available SC kVA: 500 / 0.05 = 10,000 kVA