## Power Factor Correction

Low power factor means the utility must deliver more current (and apparent power) than the load actually uses. Capacitor banks supply reactive power locally.

### Formula

**kVAR needed = kW x (tan(arccos(PF_current)) - tan(arccos(PF_target)))**

### Benefits
- Reduced utility power factor penalties
- Lower line current (smaller cables, less loss)
- Freed transformer and distribution capacity

Most utilities penalize power factors below 0.90. Correcting to 0.95 is a common economic target.

हल किया गया उदाहरण

100 kW load at PF 0.75, correcting to PF 0.95.

  1. Current angle: arccos(0.75) = 41.41 degrees, tan = 0.8819
  2. Target angle: arccos(0.95) = 18.19 degrees, tan = 0.3287
  3. kVAR needed: 100 x (0.8819 - 0.3287) = 55.3 kVAR
  4. kVA reduction: 100/0.75 - 100/0.95 = 133.3 - 105.3 = 28.1 kVA