Ventilation Rate Calculator
Calculate the required outdoor air ventilation rate for a space per ASHRAE Standard 62.1 guidelines.
sq ft
people
CFM
CFM
Total Outdoor Air
110 CFM
People Component50 CFM
Area Component60 CFM
Total Outdoor Air vs Floor Area
सूत्र
## ASHRAE 62.1 Ventilation **Outdoor Air = (People x CFM/person) + (Area x CFM/sqft)** ASHRAE 62.1 uses a two-part calculation: a per-person rate for bioeffluents and a per-area rate for building emissions. Office spaces typically use 5 CFM/person and 0.06 CFM/sqft.
हल किया गया उदाहरण
1,000 sq ft office with 10 occupants.
- 01People = 10 x 5 = 50 CFM
- 02Area = 1000 x 0.06 = 60 CFM
- 03Total = 50 + 60 = 110 CFM outdoor air