Ventilation Rate Calculator

Calculate the required outdoor air ventilation rate for a space per ASHRAE Standard 62.1 guidelines.

sq ft
people
CFM
CFM

Total Outdoor Air

110 CFM

People Component50 CFM
Area Component60 CFM

Total Outdoor Air vs Floor Area

सूत्र

## ASHRAE 62.1 Ventilation **Outdoor Air = (People x CFM/person) + (Area x CFM/sqft)** ASHRAE 62.1 uses a two-part calculation: a per-person rate for bioeffluents and a per-area rate for building emissions. Office spaces typically use 5 CFM/person and 0.06 CFM/sqft.

हल किया गया उदाहरण

1,000 sq ft office with 10 occupants.

  1. 01People = 10 x 5 = 50 CFM
  2. 02Area = 1000 x 0.06 = 60 CFM
  3. 03Total = 50 + 60 = 110 CFM outdoor air