Calculadora de Bitola de FioFormula

## Wire Gauge Selection

**CM = 2 x K x I x D / Vdrop**

Where K = 10.8 (copper resistivity constant), I is current in amps, D is one-way distance in feet, and Vdrop is the allowable voltage drop in volts. Compare the resulting circular mils to an AWG table to pick the minimum wire size.

Exemplo Resolvido

20A circuit, 50 ft run, 120V, 3% max drop.

  1. Allowable drop = 120 x 0.03 = 3.6V
  2. CM = 2 x 10.8 x 20 x 50 / 3.6 = 6,000 CM
  3. 12 AWG = 6,530 CM, which satisfies the requirement
  4. Use 12 AWG copper wire.