Calculadora de Perda de Carga por Atrito Grátis
Calcule a perda de carga por atrito em tubulações. Informe diâmetro, comprimento e vazão para o resultado.
Total Head Loss
0.00 ft
Total Head Loss vs Flow Rate
Formula
## Hazen-Williams Formula **h_f = 10.67 x (Q / C)^1.852 / D^4.8655 x L** This empirical formula is widely used for water distribution systems. C is the roughness coefficient (150 for new PVC, 130 for copper, 100 for old steel). Results are in feet of head; multiply by 0.4333 for psi.
Exemplo Resolvido
15 GPM through 1-inch copper (C=130) for 100 feet.
- 01h_f/100ft = 10.67 x (15/130)^1.852 / (1/12)^4.8655
- 02Compute numerator and denominator using the formula
- 03Total head loss for 100 ft is approximately 12.5 ft
- 04Pressure loss = 12.5 x 0.4333 = 5.42 psi
Perguntas Frequentes
What C-value should I use?
New PVC: 150, new copper: 130, new steel: 120, old cast iron: 80 to 100. Lower C values represent rougher or older pipes.
When should I use Hazen-Williams vs Darcy-Weisbach?
Hazen-Williams is simpler and widely used for water at normal temperatures. Darcy-Weisbach is more general and works for any fluid or temperature.