Short Circuit Current Calculator Formula

Understand the math behind the short circuit current calculator. Each variable explained with a worked example.

Formulas Used

Full Load Current

fla = full_load_current

Prospective Short-Circuit Current

isc = full_load_current / (impedance_pct / 100)

Short-Circuit Current

isc_ka = full_load_current / (impedance_pct / 100) / 1000

Variables

VariableDescriptionDefault
transformer_kvaTransformer Rating(kVA)500
voltageSecondary Voltage(V)400
impedance_pctTransformer Impedance(%)5
full_load_currentDerived value= transformer_kva * 1000 / (sqrt(3) * voltage)calculated

How It Works

Transformer Short-Circuit Current

The prospective short-circuit current at the transformer secondary is limited by the transformer impedance.

Formulas

I_FL = kVA x 1000 / (sqrt(3) x V) (full load current)

I_SC = I_FL / (Z%/100) (short-circuit current)

where Z% is the transformer impedance expressed as a percentage. This is the maximum fault current available at the transformer terminals, ignoring cable impedance downstream.

Worked Example

A 500 kVA transformer, 400 V secondary, 5% impedance.

transformer_kva = 500voltage = 400impedance_pct = 5
  1. 01I_FL = 500,000 / (1.732 x 400) = 721.7 A
  2. 02I_SC = 721.7 / 0.05 = 14,434 A = 14.43 kA
  3. 03Switchgear must have a breaking capacity above 14.43 kA.

Ready to run the numbers?

Open Short Circuit Current Calculator