Motor Starting Current Calculator
Calculate the inrush (starting) current of an electric motor from its nameplate data and starting method.
HP
V
%
DOL=6-8x, Soft start=2-3x, VFD=1-1.5x
Full Load Current (FLA)
11.7 A
Starting (Inrush) Current70.4 A
Starting kVA Demand58.5 kVA
Input Power8.29 kW
Full Load Current (FLA) vs Motor Horsepower
Motor Starting Current
Electric motors draw significantly more current during startup than at full speed. This inrush can be 6-8 times the full-load current.
Formulas
FLA (3-phase) = HP x 746 / (sqrt(3) x V x Eff x PF)
Starting Current = FLA x Multiplier
Starting Methods and Multipliers
Example Calculation
10 HP motor, 480 V 3-phase, 90% efficient, PF 0.85, DOL start (6x).
- 01Motor watts: 10 x 746 = 7,460 W
- 02FLA: 7460 / (1.732 x 480 x 0.90 x 0.85) = 7460 / 635.6 = 11.7 A
- 03Starting current: 11.7 x 6 = 70.4 A
- 04Starting kVA: 70.4 x 1.732 x 480 / 1000 = 58.5 kVA