Motor Starting Current Calculator

Calculate the inrush (starting) current of an electric motor from its nameplate data and starting method.

HP
V
%

DOL=6-8x, Soft start=2-3x, VFD=1-1.5x

Full Load Current (FLA)

11.7 A

Starting (Inrush) Current70.4 A
Starting kVA Demand58.5 kVA
Input Power8.29 kW

Full Load Current (FLA) vs Motor Horsepower

Motor Starting Current

Electric motors draw significantly more current during startup than at full speed. This inrush can be 6-8 times the full-load current.

Formulas

FLA (3-phase) = HP x 746 / (sqrt(3) x V x Eff x PF)

Starting Current = FLA x Multiplier

Starting Methods and Multipliers

  • Direct-On-Line (DOL): 6-8x FLA
  • Star-Delta: 2-3x (reduced torque)
  • Soft Starter: 2-4x (adjustable)
  • VFD: 1-1.5x (best control)
  • Example Calculation

    10 HP motor, 480 V 3-phase, 90% efficient, PF 0.85, DOL start (6x).

    1. 01Motor watts: 10 x 746 = 7,460 W
    2. 02FLA: 7460 / (1.732 x 480 x 0.90 x 0.85) = 7460 / 635.6 = 11.7 A
    3. 03Starting current: 11.7 x 6 = 70.4 A
    4. 04Starting kVA: 70.4 x 1.732 x 480 / 1000 = 58.5 kVA