免费换气次数计算器
计算房间的每小时换气次数和通风量。
所需风量
1,080 m^3/h
Required Airflow vs Room Length
公式
## Air Changes per Hour (ACH) ACH defines how many times the entire room volume of air is replaced per hour. ### Formula **Airflow = Room Volume x ACH** Required ACH depends on the room function. Adequate ventilation controls temperature, humidity, odours, and airborne contaminants.
计算示例
A 10m x 6m x 3m room requiring 6 air changes per hour.
- 01Volume = 10 x 6 x 3 = 180 m^3
- 02Airflow = 180 x 6 = 1080 m^3/h
- 03Airflow = 1080 / 3.6 = 300 L/s
常见问题
What ACH is required for different spaces?
Office: 4-6 ACH. Classroom: 6-8. Kitchen (commercial): 15-30. Workshop: 8-12. Hospital operating room: 15-25. Toilet/bathroom: 8-15. Warehouse: 2-4.
Is higher ACH always better?
Not necessarily. Excessive air changes waste energy by conditioning (heating/cooling) more air than needed. Balance indoor air quality needs against energy efficiency.
How does this relate to CO2 levels?
Ventilation removes CO2 exhaled by occupants. ASHRAE recommends keeping CO2 below 1000 ppm. The required outdoor air per person (typically 8-10 L/s/person) may give a different answer than ACH-based calculations.