Cable Ampacity Estimation
Ampacity is the maximum continuous current a conductor can carry without exceeding its temperature rating.
Formula
Ampacity = Cross Section x Current Density x Derating Factor
Current Density Guidelines
Derating Factors
Always verify with NEC/IEC tables for your specific installation.
计算示例
6 mm^2 copper cable, 5 A/mm^2, derating 0.8, at 230 V.
- 01Base ampacity: 6 x 5 = 30 A
- 02Derated: 30 x 0.8 = 24 A
- 03Max power: 24 x 230 = 5,520 W = 5.52 kW
常见问题
Is this a substitute for NEC/IEC tables?
No. This provides estimates. Always use the applicable electrical code tables for final cable sizing in real installations.
What happens if I exceed ampacity?
The cable overheats, insulation degrades, and eventually a fire hazard develops. Overcurrent protection (breakers/fuses) should prevent this.
How does cable length affect sizing?
Longer cables have more resistance, causing voltage drop. You may need to upsize the cable beyond ampacity requirements to limit voltage drop.