免费排风扇选型计算器

根据房间面积和用途选择合适的排风扇功率。

ft
ft
ft
ACH

Fan Rating Needed

85 CFM

房间体积640 cu ft
CFM per Sq Ft Rule80 CFM

Fan Rating Needed vs Room Length

公式

## Exhaust Fan Sizing **CFM = Room Volume x ACH / 60** The HVI (Home Ventilating Institute) recommends a simpler rule for bathrooms: 1 CFM per square foot for rooms up to 100 sq ft, and 50 CFM minimum. For larger bathrooms, add 50 CFM per fixture (toilet, shower, tub). Kitchens need 100-400 CFM depending on cooking.

计算示例

10 x 8 ft bathroom, 8 ft ceiling, 8 ACH.

  1. 01Volume = 10 x 8 x 8 = 640 cu ft
  2. 02CFM = 640 x 8 / 60 = 85 CFM
  3. 03Square foot rule = 80 CFM
  4. 04Use at least an 80-90 CFM fan.

常见问题

What sone rating is quiet?

Under 1.0 sone is considered very quiet (leaves rustling). 1-2 sones is quiet operation. Above 3 sones is noticeable. Look for fans rated under 1.5 sones for bathrooms.

Does duct length affect fan performance?

Yes. Longer duct runs and more elbows create back-pressure that reduces actual airflow. Check the fan performance curve at your estimated static pressure, typically 0.1 to 0.25 inches of water.