电气负荷计算器 — 公式
Electrical Load Formula
Amps = Watts / Volts
NEC Safety Factor = 125% (for continuous loads)
Breaker sizes are standard: 15A, 20A, 30A, 40A, 50A. Always round up to the next standard size.
计算示例
1,500W load on a 120V circuit with 125% safety factor.
- Amps = 1,500W / 120V = 12.5A
- With safety = 12.5 × 1.25 = 15.6A
- Recommended breaker = 20A